    The reason and check method of inverter low voltage and overload trip

    2023-05-20 12:17:11

    Reasons for inverter low voltage trip


    1. The low voltage of the inverter mainly refers to the low voltage of the intermediate DC circuit. Generally, the reason for the low voltage of the intermediate DC circuit comes from two aspects:


    (1) Low voltage from the power input side


    Under normal circumstances, the power supply voltage is 380V, and the allowable error is -15%~10%. After three-phase bridge full-wave rectification, the intermediate DC voltage value is 513V. In some cases, the power line voltage is small and the voltage fluctuation will not be The low voltage trip of the inverter will only cause the inverter to operate if the effective value of the grid voltage is between 80% and 85% of the rated value and the duration exceeds one cycle. The low voltage on the input side of the power supply is mainly due to the fluctuation of the grid voltage or the switching of the main power line, the power supply sine wave amplitude is affected by the lightning strike, the transformer of the power plant itself is overloaded or the load is unbalanced, etc.


    (2) Low voltage from the load side


    The reasons for this are mainly the start-up and application of large equipment, line overload, or starting large motors. The frequency converter is composed of rectifier and inverter. Through the research of the inverter, the low voltage of the inverter refers to the low voltage of the middle DC loop (that is, the input voltage of the inverter is too low). General frequency converters have protection functions of overvoltage, loss of voltage and instantaneous power failure. The inverter device of the inverter is divided into GTR and IGBT. When the inverter device of the inverter is GTR, once the voltage is lost or the power is cut off, the control circuit will stop outputting the signal to the drive circuit, so that the drive circuit and GTR all stop working, the motor It will be in free braking state. When the inverter device is IGBT, after the voltage loss or power failure, the inverter will be allowed to continue to work for a short time td. If the voltage loss or power failure time is totd, the inverter will protect itself and stop running. Generally, td is between 15 and 25 ms, and the power supply “shaking” time is generally more than a few seconds. The inverter will protect itself and stop running, so that the motor stops. Therefore, to solve the problem of inverter low voltage trip can not start from the inverter's inherent time td and voltage loss time to, but must start from the amplitude of the voltage drop.


    2. Solutions for inverter low voltage trip:


    There are two key points to be solved to solve the problem of inverter low voltage trip:


    (1) It is necessary to select the inverter with IGBT inverter device;


    (2) It is necessary to select the inverter that can still work normally under the condition of large voltage loss.


    The motor can rotate, but the running current exceeds the rated value, which is called overload. The basic reflection of overload is that although the current exceeds the rated value, the magnitude of the excess is not large, and generally a large inrush current is not formed.


    The reason and inspection method of inverter overload trip


    1. The main reason for inverter overload


    (1) Malfunction, the current detection part inside the inverter fails, and the detected current signal is too large, causing a trip.


    (2) The mechanical load is too heavy. The main feature of the heavy load is that the motor heats up and can be found by reading the running current from the display.


    (3) The three-phase voltage is unbalanced, which causes the operating current of a certain phase to be too large, resulting in overload tripping. It is characterized by unbalanced motor heating, which may not be found when the operating current is read from the display (because the display only shows one Phase current).


    2. Check method of whether the inverter is overloaded


    (1) Check whether the three-phase voltage on the motor side is balanced. If the three-phase voltage on the motor side is unbalanced, then check whether the three-phase voltage on the output side of the inverter is balanced. If it is not balanced, the problem is within the inverter.


    If the voltage at the output of the inverter is balanced, the problem lies in the line from the inverter to the motor. Check whether the screws of all terminals are tightened. If there is a contactor or other electrical appliances between the inverter and the motor, It should be checked whether the terminals of the related electrical appliances have been tightened and the contact conditions of the contacts are good.


    If the three-phase voltage on the motor side is balanced, you should understand the operating frequency at the time of tripping: if the operating frequency is low and vector control (or no vector control) is not used, first reduce the U/f ratio, if it can still drive the load , It means that the original preset U/f ratio is too high, the peak value of the excitation current is too large, and the current can be reduced by reducing the U/f ratio;


    If the load can not be moved after the reduction, you should consider increasing the capacity of the inverter; if the inverter has vector control function, the vector control method should be used.


    (2) Check whether the motor heats up. If the temperature rise of the motor is not high, first check whether the electronic thermal protection function of the inverter is preset properly. If the inverter still has a margin, the preheating of the electronic thermal protection function should be relaxed. Set value.


    If the temperature rise of the motor is too high, and the overload is normal overload, it means that the motor is overloaded. At this time, whether the transmission ratio should be properly increased to reduce the load on the motor shaft. If it can be increased, increase the transmission ratio. If the transmission ratio cannot be increased, the capacity of the motor should be increased.


    General purpose frequency converter


    label

    QR code

    The public,

    Mobile station
    The public, Mobile station

    Contact

    未標題-8.png 0755-81719517
    未標題-10.png0755-81719530 未標題-11.pngamb@ambition.com.cn
    未標題-12.pngFloor 1, 5 and 6, building 7, lijincheng science and technology industrial park, gongye dong road, longhua new district, shenzhen

    Navigation

    Home          About

    Product      Case

    Solution      Service

    Job      News

    Contact          

    Copyright © Shenzhen Ambition Electronic Co., Ltd Record number:備案號:粵ICP備12045920號
    主站蜘蛛池模板: 高清国产在线拍揄自揄视频| 亚洲va中文字幕| 无码专区heyzo色欲av| 五月天天爽天天狠久久久综合| 无码国产成人午夜在线观看| 国产成人高清在线观看视频| 久久精品免视看国产成人| 中国精品18videosex性中国| 尹人香蕉久久99天天拍| 国产精品久久久久久影视| 人妻熟女一区二区aⅴ向井蓝| 国产日韩精品一区二区三区在线| 久久婷婷五月综合色高清| 熟女系列丰满熟妇av| 亚洲精品精华液一区二区| 99精品视频在线观看免费蜜桃| 成人免费乱码大片a毛片| www国产精品人妻一二三区| 最新色国产精品精品视频| 亚洲天堂在线观看完整版 | 野外性史欧美k8播放| 国产精品亚洲欧美中字| 欧美人与动性xxxxbbbb| 国产亚洲综合久久系列| 国产sp调教打屁股视频网站| 日韩精品无码一区二区三区免费 | 国产精品电影久久久久电影网| 亚洲AV成人片不卡无码| 中国熟女仑乱hd| 国产精品美女久久久久av福利 | 日本日本乱码伦专区| 免费床视频大全叫不停欧美| 国产人久久人人人人爽| 国产综合无码一区二区辣椒| 香蕉影院在线观看| 麻豆国产在线精品国偷产拍| 国产成人无码3000部| 亚洲成A人片在线观看的电影| 国产老太一性一交一乱| 公天天吃我奶躁我的在线观看| 视频二区精品中文字幕|